DILM40(RDC24) - Stycznik mocy, I=40A (AC-3)

  • szt.
  • Rabat: -448,80 zł (40 %)
  • (Rabat brutto: -552,02 zł (40 %))
  • Cena brutto: 828,04 zł / szt. 673,20 zł / szt.
Stycznik mocy, I=40A [AC-3] DILM40(RDC24)
Program
Product range
  Contactors
Application
  Contactors for Motors
Subrange
  Contactors up to 170 A, 3 pole
Connection technique
  Screw terminals
Pole
  3 pole
Rated operational current
   
AC-3
   
380 V 400 V
IeA40
AC-1
   
Conventional free air thermal current, 3 pole, 50 - 60 Hz
   
Open
   
at 60 °C
Ith =IeA50
Max. rating for three-phase motors, 50 - 60 Hz
   
AC-3
   
220 V 230 V
PkW12.5
380 V 400 V
PkW18.5
660 V 690 V
PkW23
AC-4
   
220 V 230 V
PkW5
380 V 400 V
PkW9
660 V 690 V
PkW12
Contact sequence
  
Instructions
  Contacts to EN 50 012.
integrated suppressor circuit in actuating electronics
Can be combined with auxiliary contact
  DILM150-XHI(V)..
DILM1000-XHI(V)..
Voltage AC/DC
  DC operation
Approbationen
Product StandardsIEC/EN 60947-4-1; UL 508; CSA-C22.2 No. 14-05; CE marking
UL File No.E29096
UL CCNNLDX
CSA File No.012528
CSA Class No.2411-03, 3211-04
NA CertificationUL Listed, CSA certified
Specially designed for NANo
 
General
Standards
  IEC/EN 60947, VDE 0660, UL, CSA
Lifespan, mechanical
   
AC operated
Operationsx 10610
DC operated
Operationsx 10610
Operating frequency, mechanical
   
AC operated
Operations/h 5000
DC operated
Operations/h 5000
Climatic proofing
  Damp heat, constant to IEC 60068-2-78
Damp heat, cyclic to IEC 60068-2-30
Ambient temperature
 °C 
Open
 °C-25- 60
Enclosed
 °C-25- 40
Storage
 °C-40- 80
Mounting position, AC- and DC operated
  
Mechanical shock resistance (IEC/EN 60068-2-27)
   
Half-sinusoidal shock, 10 ms
   
Main contacts
   
N/O contact
 g10
Auxiliary contacts
   
N/O contact
 g7
N/C contact
 g5
Mechanical shock resistance (IEC/EN 60068-2-27) when tabletop-mounted
   
Half-sinusoidal shock, 10 ms
   
Main contacts
   
N/O contact
 g10
Auxiliary contacts
   
N/O contact
 g7
N/C contact
 g5
Protection type
  IP00
Protection against direct contact when actuated from front (EN 90274)
  Finger- and back-of-hand proof
Weight
   
AC operated
 kg0.9
DC operated
 kg1.1
Terminal capacity main cable
   
Solid
 mm21 x (0.75 - 16)
2 x (0.75 - 16)
Flexible with ferrule
 mm21 x (0.75 - 35)
2 x (0.75 - 25)
Stranded
 mm21 x (16 - 50)
2 x (16 - 35)
Solid or stranded
 AWG12 - 2
Flat conductor
Number of segments x width x thickness mm2 x (6 x 9 x 0.8)
Main cable connection screw/bolt
  M6
Tightening torque
 Nm3.3
Terminal capacity control circuit cables
   
Solid
 mm21 x (0.75 - 4)
2 x (0.75 - 4)
Flexible with ferrule
 mm21 x (0.75 - 2.5)
2 x (0.75 - 2.5)
Solid or stranded
 AWG18 - 14
Control circuit cable connection screw/bolt
  M3.5
Tightening torque
 Nm1.2
Tool
   
Main cable
   
Pozidriv screwdriver
 Size2
Standard screwdriver
 mm0.8 x 5.5
1 x 6
Control circuit cables
   
Pozidriv screwdriver
 Size2
Standard screwdriver
 mm0.8 x 5.5
1 x 6
Terminal capacity control circuit cables
   
Solid
 mm21 x (0.75 - 2.5)
2 x (0.75 - 2.5)
Flexible
 mm21 x (0.75 - 2.5)
2 x (0.75 - 2.5)
Flexible with ferrule
 mm21 x (0.75 - 1.5)
2 x (0.75 - 1.5)
Solid or stranded
 AWG18 - 14
Tool
   
Stripping length
 mm10
Screwdriver blade width
 mm3.5
Main conducting paths
Rated impulse withstand voltage
UimpV AC8000
Overvoltage category/pollution degree
  III/3
Rated insulation voltage
UiV AC690
Rated operational voltage
UeV AC690
Safe isolation to VDE 0106 Part 101 and Part 101/A1
   
between coil and contacts
 V AC440
between the contacts
 V AC440
Making capacity (p.f. to IEC/EN 60947)
   
 
Up to 690 VA560
Breaking capacity
   
220/230 V
 A400
380/400 V
 A400
500 V
 A400
660/690 V
 A250
Short-circuit rating
   
Short-circuit protection maximum fuse
   
Type “2” coordination
   
400 V
gG/gL 500 VA 63
690 V
gG/gL 690 VA 50
Type “1” coordination
   
400 V
gG/gL 500 VA 125
690 V
gG/gL 690 VA 80
AC
AC-1 duty
   
Conventional free air thermal current, 3 pole, 50 - 60 Hz
   
Open
   
at 40 °C
Ith =IeA60
at 50 °C
Ith =IeA57
at 55 °C
Ith =IeA55
at 60 °C
Ith =IeA50
enclosed
IthA45
Conventional free air thermal current, 1 pole
   
open
IthA125
enclosed
IthA112
AC-3 duty
   
Rated operational current AC-3 open, 50 - 60 Hz, 3 pole
Ie  
220/230 V
IeA40
240 V
IeA40
380/400 V
IeA40
415 V
IeA40
440V
IeA40
500 V
IeA40
660/690 V
IeA25
Motor rating
PkWh 
220/230 V
PkW12.5
240V
PkW13.5
380/400 V
PkW18.5
415 V
PkW24
440 V
PkW25
500 V
PkW28
660/690 V
PkW23
AC-4 duty
   
Rated operational current AC-4 open, 50 - 60 Hz, 3 pole
Ie  
220/230 V
IeA18
240 V
IeA18
380/400 V
IeA18
415 V
IeA18
440 V
IeA18
500 V
IeA18
660/690 V
IeA14
Motor rating
PkWh 
220/230 V
PkW5
240 V
PkW5.5
380/400 V
PkW9
415 V
PkW9.5
440 V
PkW10
500 V
PkW11
660/690 V
PkW12
DC
Rated operational current, open
   
DC-1 operation
   
60 V
IeA50
110 V
IeA50
220 V
IeA45
440 V
IeA2.9
DC-3 operation
   
60 V
IeA50
110 V
IeA50
220 V
IeA25
440 V
IeA0.6
DC-5 operation
   
60 V
IeA50
110 V
IeA50
220 V
IeA25
440 V
IeA0.6
Current heat loss (3 pole)
Current heat loss at Ith
 W11.3
Current heat loss at Ieto AC-3/400 V
 W7.2
Impedance per pole
 mΩ1.5
Magnet systems
Voltage tolerance
 x Uc 
AC operated
Pick-upx Uc0.8- 1.1
Drop-out voltage AC operated
Drop-outx Uc0.3- 0.6
Notes
  RDC 24 (Umin24 V DC/Umax27 V DC)
Example: Uc= 0.7 x Umin- 1.2 x Umax/ Uc= 0.7 x 24 V - 1.2 x 27 V DC
DC operated
Pick-upx Uc0.7- 1.2
Notes
  at least smoothed two-phase bridge rectifier or three-phase rectifier
DC operated
Drop-outx Uc0.15- 0.6
Power consumption of the coil in a cold state and 1.0 x Uc
   
50 Hz
Pick-upVA149
50 Hz
SealingVA16
50 Hz
SealingW4.3
60 Hz
Pick-upVA178
60 Hz
SealingVA19
60 Hz
SealingW5.3
50/60 Hz
Pick-upVA168
154
50/60 Hz
SealingVA22
14
50/60 Hz
SealingW5.3
4.3
DC operated
Pick-upW24
DC operated
SealingW0.5
Duty factor
 % DF100
Switching times at 100 % Uc(approximate values)
   
Main contacts
   
AC operated
   
Closing delay
 ms12- 18
Opening delay
 ms8- 13
DC operated
 ms 
Closing delay
 ms54
Opening delay
 ms24
Arcing time
 ms10
Lifespan, mechanical; Coil 50/60 Hz
at 50 Hz Mechanical lifespan at 50 Hz approx. 30% lower than under “Technical data, general”
Electromagnetic compatibility (EMC)
Emitted interference
  to EN 60947-1
Interference immunity
  to EN 60947-1
Technical data according to ETIM 4.0
Number of main contacts as N/Os
  3
Rated operation current Ie at AC-1, 400 V
  60
Connection type main circuit
  Screw connection
Rated control voltage Us at AC 60HZ
 V0
Number of auxiliary contacts as N/Os
  0
Rated control voltage Us at AC 50HZ
 V0
Number of auxiliary contacts as N/Cs
  0
Suitable for rail-mounting
  No
Rated control voltage Us at DC
 V27
Voltage type for actuation
  DC
Rated operation current Ie at AC-3, 400 V
 A40
Number of N/Cs as main contact
  0
Motor rating at AC-3, 400 V
 kWh18.5
Characteristics
1: Overload relay
2: Suppressor
3: Auxiliary contact modules
on the side: 2 x DILM1000-XHI(V)11-SI; surface mounting: 1 x DILM150-XHIA11
on the side: 2 x DILM1000-XHI(V)11-SA; surface mounting: 1 x DILM150-XHI (2 pole)
on the side: 1 x DILM1000-XHI(V)11-SI; surface mounting: 1 x DILM150-XHIA22
on the side: 1 x DILM1000-XHI(V)11-SA; surface mounting: 1 x DILM150-XHI (4 pole)
Projektieren
Squirrel-cage motor
Operating characteristics
Starting:from rest
Stopping:after attaining full running speed
Electrical characteristics
Make: up to 6 x rated motor current
Break: up to 1 x rated motor current
Utilization category
100 % AC-3
Typical applications
Compressors
Lifts
Mixers
Pumps
Escalators
Agitators
Fans
Conveyor belts
Centrifuges
Hinged flaps
Bucket-elevators
Air conditioning system
General drives in manufacturing and processing machines
Extreme switching duty
Squirrel-cage motor
Operating characteristics
Inching, plugging, reversing
Electrical characteristics
Make: up to 6 x rated motor current
Break: up to 6 x rated motor current
Utilization category
100 % AC-4
Typical applications
Printing presses
Wire-drawing machines
Centrifuges
Special drives for manufacturing and processing machines
Dimensions
Contactor with auxiliary contact module
Lateral clearance to earthed parts: 6 mm
DILM40…DILM72
DILMC40…DILMC65
DILMF40…DILMF65

Opis pochodzi ze strony www.moeller.net .