3-faz. trafo sterujący,separ. i bezp.

  • szt.
  • Rabat: -1 401,60 zł (40 %)
  • (Rabat brutto: -1 723,97 zł (40 %))
  • Cena brutto: 2 585,95 zł / szt. 2 102,40 zł / szt.
3-faz. trafo sterujący,separ. i bezpiecz.(DTZ) DTZ0,63(*/*)*
Program
Range
  Three-phase DTZ control transformers
Rated input voltage
 V50 – 950 ± 5 %
Rated output voltage
 V50 – 950
Rated power
 kVA0.63
Short-time rating
 kVA1.38
Cu factor3,00
Notes
  • Transformers with the rated output voltages 50 V can be used as safety transformers to IEC/EN 61558.
  • UL/CSA only up to primary and secondary 600 V (incl. tapping).
  • Enclosures IP65 on request.

When ordering, the type reference must include the following details:

DTZ0,1(*/*)*

1st wildcard Nominal input voltage

2nd wildcard Rated output voltage

3rd wildcard Configuration

Ordering example

  • Desired part no. DTZ0,1
  • Desired rated input voltage 200 V
  • Desired rated output voltage 18.5 V
  • Desired configuration Dy(n)5

The correct type reference is

DTZ0,1(200/18,5)DY(N)5

Additional tappings → 931897

Approbationen
Product StandardsUL 506; UL5085-1; UL 5085-2; CSA-C22.2 No. 66; CSA-C22.2 No. 66.1-06; CSA-C22.2 No. 66.2-06; IEC/EN 61558-2-2; CE marking
UL File No.E167225
UL CCNXPTQ2, XPTQ8
CSA File No.UL report applies to both US and Canada
CSA Class No.
NA CertificationUL Recognized, certified by UL for use in Canada
Specially designed for NANo
Suitable forBranch circuits
Max. Voltage Rating600 V AC
Degree of ProtectionIEC: IP00, UL/CSA Type: -
 
General
Standards
   
Built and tested to
  IEC/EN 61558-2-2/2-4/2-6
VDE 0570 Part 2-2
VDE 0570 Part 2‐6 (safety transformers)
VDE 0570 Part 2-4 (isolating transformer)
Suitable for use to
  IEC/EN 60204-1, ÖVE-EN 13
VDE 0113, VDE 0100 Part 410
Ambient temperature
 °C-25- 40
Characteristics
Terminations
  ● (< 115 A)
Connection lugs
  ● (> 115 A)
Insulation class
  B
Rated frequency
 Hz50- 60
Primary tapping
  ± 5 %
Protection type
  IP00
Separate windings
  
Fully vacuum-impregnated
  
Reinforced insulation
  
Rated duty factor
 % DF100
Electrical characteristics
Note
  The following applies for the no-load loss, short-circuit loss (copper losses), short-circuit voltage and efficiency values: all details relate to a temperature of 20 °C
Total weight
 kg8.9
No-load losses
 W25
Short-circuit losses
 W50
Shortcircuit voltage
 %5.5
Efficiency
  0.9
Technical data according to ETIM 4.0
Rating
 W630
Secondary voltage range 10
 V0
Primary voltage 3 from/to
 V950
Primary voltage 1 from/to
 V950
Protection type (IP)
  IP00
Primary voltage 6 from/to
 V950
Primary voltage 9 from/to
 V0
Primary voltage 5 from/to
 V950
Primary voltage 8 from/to
 V0
Secondary voltage range 4
 V1000
Height
 mm224
Circuit type
  -
Primary voltage 10 from/to
 V0
Primary voltage 2 from/to
 V950
Secondary voltage range 3
 V1000
Relative short-circuit voltage Uk
 %5.5
Secondary voltage range 1
 V1000
Built as safety transformer
  YES
Depth
 mm132
Secondary voltage range 8
 V0
Built as isolating transformer
  YES
Built as energy saving transformer
  No
Short-circuit proof
  No
Secondary voltage range 9
 V0
Primary voltage 7 from/to
 V0
Type of insulation material acc. IEC 85
  B
Secondary voltage range 2
 V1000
Width
 mm190
Secondary voltage range 7
 V0
Secondary voltage range 6
 V1000
Primary voltage 4 from/to
 V950
Secondary voltage range 5
 V1000
Dimensions
The higher rated operating voltage applies
Terminals 25 A
Connection lugs > 63 A

Opis pochodzi ze strony www.moeller.net .